Energy Savings Calculator

Estimate annual energy consumption and cost savings when upgrading from an existing HVAC system to a higher-efficiency model.

Formulas Used

Annual BTU Load:
Annual BTU = Cooling Load (tons) × 12,000 BTU/hr/ton × Operating Hours (hr/yr)

EER Conversion:
EER (BTU/Wh) ≈ SEER × 0.875
(Accounts for mixed part-load vs. full-load operation per AHRI Standard 210/240)

Annual Energy Consumption:
kWh = Annual BTU Load ÷ (EER × 1,000)

Annual Savings:
ΔkWh = kWhold − kWhnew
ΔCost ($) = ΔkWh × Electricity Rate ($/kWh)

Assumptions & References

  • SEER-to-EER conversion factor of 0.875 is an industry-standard approximation per AHRI Standard 210/240 and widely used in DOE energy analyses.
  • Minimum federal SEER standard for residential central AC (as of 2023): 14 SEER (North) / 15 SEER (South) per DOE 10 CFR Part 430.