Cooling Tower Efficiency Calculator

Calculate cooling tower efficiency (effectiveness), range, approach temperature, and heat rejection rate based on inlet/outlet water temperatures, wet-bulb temperature, and flow rate.

Formulas Used

Range (°F):

Range = Thot,in − Tcold,out

Approach (°F):

Approach = Tcold,out − Twb

Cooling Tower Efficiency (Effectiveness):

η = Range / (Range + Approach) × 100 = (Thot,in − Tcold,out) / (Thot,in − Twb) × 100

Heat Rejection Rate:

Q (BTU/hr) = GPM × 500.4 × Range

where 500.4 = 8.34 lb/gal × 60 min/hr × 1 BTU/(lb·°F) (specific heat of water)

Q (Tons) = Q (BTU/hr) / 12,000  |  Q (kW) = Q (BTU/hr) × 0.000293071

Number of Transfer Units (NTU) — Merkel simplified:

NTU = Range / Approach

(Valid approximation when the operating line and equilibrium line are approximately parallel.)

Assumptions & References

  • Water is assumed to have a specific heat (Cp) of 1.0 BTU/(lb·°F) and a density of 8.34 lb/gal.
  • References: ASHRAE Handbook — HVAC Systems and Equipment (Chapter: Cooling Towers); Cooling Technology Institute (CTI) Standard STD-201; Merkel, F. (1925). Verdunstungskühlung.